BMS · BMS integrator (confidential)
Form 2 Siemens BMS panels for a hospital refurbishment
A BMS integrator was replacing the building controls in a hospital refurbishment. We designed and manufactured the two BMS panels for the plant room: Siemens PXC7 controllers, Form 2 segregated, with surge protection and full manual control from the door.
- Site
- Hospital refurbishment
- Panels
- 2, Form 2, one a two-enclosure suite
- Controls
- Siemens PXC7 with TX-I/O
- Largest
- 1800x1200 + 1800x600mm
The challenge
BMS panels for a hospital refurbishment, controlling air handling units, pumps and smoke and fire damper interfaces across the plant.
What we supplied
Two Form 2 BMS panels on Siemens PXC7 controllers, the larger a two-enclosure floor-standing suite with 21 TX-I/O modules.
The result
Every item of plant on the door with hand/off/auto, enable, run and fault, and every signal on a labelled terminal.
The requirement
Two BMS panels for the refurbished plant, both Form 2 segregated, with type 2+3 surge protection and Schneider MCBs as specified. The larger is a floor-standing suite of two enclosures, 1800x1200mm double-door and 1800x600mm, with a Siemens PXC7 controller and 21 TX-I/O modules. The second is a 1000x1200mm double-door panel with a PXC7 and 10 modules.
The constraints
- A live hospital, so the panels had to be right on arrival and fully documented for the estates team.
- Manual control from the door for the air handling unit supply and extract fans and the run-around coil and LTHW pumps.
- Frost, filter and smoke detection, plus interfaces to the fire alarm and the smoke and fire damper panel.
- Form 2 segregation, surge protection and a specified make of MCB.
What we built
Both panels drawn from the integrator's points schedules and built on our standard BMS platform: the PXC7 and its TX-I/O modules, interposing relays for every enable, towers of labelled terminals for the field wiring, and an engraved door fascia giving hand/off/auto, enable, run and fault for each item of plant. Each was routine tested in Stoke-on-Trent and despatched with its wiring diagram and test certificate.
Delivery
Built and despatched one panel at a time over the summer of 2026.
The outcome
The estates team can see and run every fan and pump from the door without a laptop, and every field signal lands on a labelled terminal that matches the drawings. We can't name the hospital or the integrator; the photographs are of the panels themselves.
Photos
Got a similar job?
Send the spec, points list or drawing and we will tell you what we would build, the price and the date.
“Normally we'd expect a 6 to 8 week lead time on a panel build. In this case it was done in 12 working days, which is a testament to G&G Controls and SSE working together.”
- Wiring diagram, test certificate and 12-month warranty with every panel
- Built to BS EN 61439 and BS EN 60204-1 in Stoke-on-Trent
- We reply during working hours, usually the same working day
More case studies

Butlins Skegness
One MCCP for 64 motors in a water park plant room
The pool and water park plant room at Butlins Skegness needed a new MCCP to run every pump, blower and feature from one place, with a BMS interface for the integrator's controllers. We designed and built it in Stoke-on-Trent.
Read the case study
Confidential London project
Every BMS control panel for a prestigious London building, from one supplier
The full BMS control panel supply package for a high-profile London building: every outstation and motor control panel across its plant rooms, designed, built and tested in Stoke-on-Trent and delivered to the contractor's programme. The client and project cannot be named.
Read the case study
SSE Energy Solutions
A Form 2 outdoor BMS panel on the roof in 12 working days
SSE Energy Solutions were refitting the third floor of Highgate Mental Health Hospital in London: new walls, heating, HVAC, electrical and controls throughout, with a new BMS tying into the trust's existing Trend network. The panel for it had to sit on the roof, and the only crane was coming down in three weeks.
Read the case studyGot a project, or just need a quick answer?
Tell us what the panel has to do and we will come back with a price and a lead time. Existing accounts: reorders and spares go through the same form.