OEM and equipment manufacturers · Temporary cooling hire company
A dual chiller changeover panel, drawn once and built again and again for a hire fleet
A national cooling hire company sends chillers out in pairs, and every pair needs a changeover panel to share the load, rotate duty and take over when one trips. We took their existing panel design, re-engineered it, drew it as indoor and outdoor standards and now build it whenever their depots need more.
- Customer
- Temporary cooling hire company
- Panel
- Dual chiller changeover, indoor and outdoor
- Built so far
- 20 changeover panels, plus defrost and triple
- Typical turnaround
- 1 to 3 weeks
- Control
- Siemens LOGO!, 24V DC
The challenge
A cooling hire company needed its two-chiller changeover panel built the same way every time, ready on the shelf for urgent hires.
What we supplied
Their existing design re-engineered on 24V DC with a Siemens LOGO!, drawn once in indoor and outdoor versions, then built to order as a standard part.
The result
Twenty changeover panels and counting, built to one drawing set, typically turned round in one to three weeks.
The requirement
Two chillers on a hire site share one cooling load. The changeover panel decides which one runs, brings the second in when the first cannot keep up, swaps duty so both wear evenly and stops calling a chiller that has tripped. The hire company already had a panel design that did this, but it was being built as a one-off each time. They wanted it standardised: the same drawing, the same parts and the same wiring every time, in a version for indoors and one for outdoors, so their depots could hold panels in stock and pick one off the shelf when a job came in at short notice.
The constraints
- Their design, their product code: we were improving an existing panel, not starting again, and every change had to be agreed with their technical manager.
- The panel only enables the chillers and reads their faults; the chillers are powered separately, so the signals going out to them had to be safe to handle on site.
- A failed or disconnected fault signal had to read as a fault, not as healthy.
- Indoor and outdoor versions that an engineer could wire, test and fault-find the same way.
- Repeat orders from more than one depot and buyer, so every panel had to match the drawing exactly.
What we built
We redrew the panel with circuit breakers in place of fuses and changed the control from 110V AC to 24V DC, so the volt-free circuits out to the chillers are extra-low voltage. The logic runs on a Siemens LOGO! with display: the start signal enables the duty chiller, an over-temperature stat brings in the assist chiller, duty rotates once a week at a set day and time, a faulted chiller is never called and the healthy one becomes fixed duty, and a front switch can force chiller 1 or chiller 2. Fault inputs are fail-safe, with short delays so a flicker does not cause a changeover, and there are separate volt-free outputs for a common fault and a chiller alarm. Cable colours follow the customer's own standard. The indoor version is a steel wall box; the outdoor version is a polyester enclosure with a clear outer door. The same approach went into a triple chiller changeover panel (two running, one standby) and a defrost panel for low-temperature air cooler coils, built to the customer's drawing.
Delivery
The first standard panel set the drawing, which the customer approved before the repeat orders started. Since then the dual changeover panels have typically gone out one to three weeks from order, one at a time or in batches of two or three, with the drawing and test certificate in each.
The outcome
Twenty dual chiller changeover panels so far, nine indoor and eleven outdoor, plus triple changeover and defrost panels, all built to one set of drawings. The hire company holds them in its depots, so an urgent job can go out with a panel that is already on the shelf; one buyer ordering three more noted they already had one in stock for an urgent job.
Photos
Got a similar job?
Send the spec, points list or drawing and we will tell you what we would build, the price and the date.
- Wiring diagram, test certificate and 12-month warranty with every panel
- Built to BS EN 61439-2 and BS EN 60204-1 in Stoke-on-Trent
- We reply during working hours, usually the same working day
More case studies

Butlins Skegness
One motor control centre for 64 motors in a water park plant room
The pool and water park plant room at Butlins Skegness needed a new motor control centre to run every pump, blower and feature from one place, with a BMS interface for the integrator's controllers. We designed and built it in Stoke-on-Trent.
Read the case study
Confidential London project
Every BMS control panel for a prestigious London building, from one supplier
The full BMS control panel supply package for a high-profile London building: every outstation and motor control panel across its plant rooms, designed, built and tested in Stoke-on-Trent and delivered to the contractor's programme. The client and project cannot be named.
Read the case study
SSE Energy Solutions
A Form 2 outdoor BMS panel on the roof in 12 working days
SSE Energy Solutions were refitting the third floor of Highgate Mental Health Hospital in London: new walls, heating, HVAC, electrical and controls throughout, with a new BMS tying into the trust's existing Trend network. The panel for it had to sit on the roof, and the only crane was coming down in three weeks.
Read the case studyGot a project, or just need a quick answer?
Tell us what the panel has to do and we will come back with a price and a lead time. Existing accounts: reorders and spares go through the same form.