Skip to content
G&G Controls, The Panel People
Wastewater practice

Wiring a Basix pump control panel on site: supply, pumps and floats

By Tristan Newton, Commercial Director · 22 May 2026 · 4 min read

Wiring a Basix pump control panel on site: supply, pumps and floats

A standard wastewater pump panel has three groups of connections: the incoming supply, the pump cables and the level controls. Get those three right, in that order, and the panel will run first time. This is how we wire a Basix panel on site, and the checks we make before switching on.

First, the safety bit. Only do this if you are competent to work on low-voltage electrical equipment. Isolate and prove dead before you touch anything, and follow your own safe isolation procedure. Every G&G panel ships with its own wiring diagram and test certificate inside the door: the diagram supplied with the panel takes precedence over anything general written here. Terminal numbers below are typical, not a substitute for the drawing.

Before you start

  • Check the panel rating plate matches the pumps: number of pumps, single or three phase, and the current range of the overloads.
  • Check the enclosure is fixed level, that gland plate entries are at the bottom, and that no cable will enter from the top where water can track in.
  • Read the diagram. Two minutes now saves an hour later.

1. The incoming supply

The supply lands on the door-interlocked isolator at the top of the panel, or on incoming terminals next to it. Three phase: L1, L2, L3, N (where present) and earth. Single phase: L, N and earth.

Use the right size cable for the panel rating and the protective device feeding it, and gland it properly. The earth goes to the main earth terminal, not a spare terminal that happens to be nearby. Why multiple earths on the same stud are banned explains what inspectors look for.

Do not switch on yet.

2. The pump cables

Each pump has its own contactor and overload. The pump cable connects to the outgoing terminals below the overload for that pump, marked U, V, W (three phase) or L, N (single phase), with the pump earth to the earth bar. Pump 1 to pump 1's terminals, pump 2 to pump 2's; it sounds obvious, but swapping them is the most common wiring fault we see.

Submersible pump cables are often SWA. Gland them so the armour is earthed at the panel end. Should you gland both ends of SWA cable? covers the arguments.

If the pump has seal leak or thermal contacts, they go to the control terminals marked for them, not to the power terminals. A panel with the seal leak option will have a relay and lamp for each pump.

3. The level controls

For a float switch panel, the floats connect to the control terminals labelled for each function. A typical twin pump panel uses four:

  1. Stop (low level)
  2. Start (duty)
  3. Assist (standby)
  4. High level alarm

Floats are two-wire devices on the low-voltage control circuit. Keep their cables away from the power cables where you can, and make sure each float is on the right terminal pair. Where to hang the floats covers the levels themselves.

For a panel with a 4-20mA input, such as Basix View or Telemetrix View, the sensor cable goes to the analogue input terminals with the screen earthed at the panel end only.

4. Anything else

  • Volt-free contacts for run, fault and high level, if someone else's telemetry or a BMS needs them.
  • The beacon, if fitted, to its supply terminals.
  • Heater and light in a kiosk are usually pre-wired.

Before you switch on

  1. Every terminal tightened, every cable identified. Give each one a tug.
  2. Insulation resistance test the pump cables and motors before connecting them to the panel. A wet pump cable will trip the panel the moment you try it.
  3. Overload settings match the pump full load current on the nameplate. What you are doing wrong with overloads if you are unsure.
  4. Floats hang free and are not tangled.
  5. Panel door closed, isolator on, control circuit breaker on.

Commissioning

Turn each pump to hand in turn and check it runs and the direction is right (on a three-phase pump, wrong rotation means little or no flow; swap two phases at the pump terminals). Then set both to auto, fill the chamber and watch a full cycle: duty pump starts on the start float, stops on the stop float, the assist float brings in the second pump, the high level float raises the alarm and sounder. Check the duty changes over on the next cycle.

Write the pump full load currents and the overload settings on the commissioning sheet in the door, and leave the diagram where you found it. The next engineer will thank you.

Stuck? The technical line is 01782 320400, Monday to Friday, 7am to 4.30pm.

Frequently asked questions

Which terminal does each float go to?

It is printed on the terminal rail and shown on the diagram inside the door. On a standard twin pump Basix panel the four control pairs are stop, start, assist and high level, in that order from the left, but always check the drawing for the panel in front of you.

The pump runs in hand but not in auto. What is wrong?

Almost always the floats: a float on the wrong terminals, a float that is stuck, or the stop float not making. Lift each float by hand with the panel in auto and watch which lamp changes.

Do I need a neutral for a three-phase panel?

The standard panel uses the neutral for the 230V control circuit. If the supply has no neutral, tell us when ordering and we fit a transformer to provide it.

Can I extend the float cables?

Yes, in a proper junction box with the joint above the water line, using cable rated for the environment. Keep the joint accessible: floats are the part that gets replaced.

Written by the engineers at G&G Controls, a UK control panel manufacturer in Stoke-on-Trent. For general guidance only; consult a qualified professional for advice on your own installation.

Up next

Duty/standby, duty/assist and duty changeover explained

What the three twin-pump arrangements mean, which one your pump station should use, and why a panel that alternates the duty pump makes both pumps last longer.

Related panel

If this article is about a problem you have on site, this is the panel we would suggest.

Basix twin pump wastewater control panel with the door open, showing contactors, overloads and WAGO terminals

Wastewater control panel

Basix

The standard float-switch pump panel: industrial components, a lifetime warranty on the stepping relay, and next-day delivery from stock.

From £906 + VAT for a single pump DOL panel and £1,245 + VAT for a twin pump DOL panel.

Ask an engineer

A question about this article or a panel for your site. We reply during working hours.

Or call 01782 280577

What happens next. A price and lead time, usually the same working day. Stock panels ship next day. We reply during working hours, Monday to Friday, 7am to 4.30pm.

Your details go to our sales team by email and are used only to answer this enquiry. No mailing list, nothing shared. Privacy policy.

More on wastewater practice

Telemetry costs explained: SIM, data, texts and the Dashboard

Telemetry costs explained: SIM, data, texts and the Dashboard

No subscription for alerts, so what do you actually pay to monitor a pump station remotely? Every cost of a Telemetrix panel, with worked examples for one station and for fifty.

24 July 2026 · 4 min read

Adoptable pumping station control panels: what the water companies require

Adoptable pumping station control panels: what the water companies require

How a panel for an adoptable sewage pumping station differs from a standard one, what United Utilities, Severn Trent, Anglian Water and the other authorities look for, and how to avoid a failed handover.

17 July 2026 · 4 min read

The high level alarm has gone off: what to do

The high level alarm has gone off: what to do

A plain guide for whoever looks after the building. What the alarm means, what to check in the first five minutes, when to call someone, and how to stop it happening again.

5 June 2026 · 4 min read

Latest from the knowledge hub

Standardising a control panel platform: how OEMs take cost and lead time out
Company and industry

Standardising a control panel platform: how OEMs take cost and lead time out

Equipment makers who order panels every month usually order too many variants. How to design one platform with option blocks, what it saves, and how to move a range across to it.

21 August 2026 · 4 min read

Free-issue controllers: how it works and what we need from you
BMS

Free-issue controllers: how it works and what we need from you

Sending your own Trend, Distech, ISMA or Tridium controllers to be fitted into a panel: what to send, when, how it is labelled and tested, and who is responsible for what.

14 August 2026 · 4 min read

What's inside a BMS outstation panel
BMS

What's inside a BMS outstation panel

Power supplies, surge protection, a network switch, the controller and the terminals: what each part of a BMS panel does, and why the bits around the controller matter as much as the controller.

7 August 2026 · 4 min read

All 66 articles →